The Shand & Jurs Biogas Detonation Flame Arresters provide
protection against flame propagation through piping runs and vapor recovery
systems, while allowing maximum flow efficiencies. This design quenches a flame
front approaching from either direction, even if it has transitioned to a
detonation. The Arresters contain a detonation while retaining the integrity
of both the arresting element and the housing. This is ensured by the design
of the passages in the tube bank and the detonation resistant construction.
Standard construction of the housing is available in Carbon Steel or 316
Stainless Steel. The tube bank is Stainless Steel throughout. Special
construction materials to withstand the corrosive actions of some vapors
and atmospheric conditions are available upon request.
Because of the severe
service conditions that the Detonation Flame Arrester encounters, all
construction welding is performed in accordance with ASME Boiler and Pressure
Vessel Code Section Vlll and IX. Class 150lb. hydrostatically tested at 425
psig. Class 300lb. hydrostatically tested at 750 psig.
These models are
available in a range of sizes from 2" through 24". Additional sizes available
upon request. Standard connections are ANSI 150lb. or 300lb. Class raised face
flanges.
|