The Shand & Jurs Model 94307 Horizontal Flame Arrester is
designed to provide a positive flame stop in gas piping systems.
Model 94307 not only provides exceptional protection against propagation
of fire, but also offers maximum flow capacity. It is specifically designed to
prevent liquid accumulation in the tube bank assembly.
The tube bank design,
consisting of a spiral wound crimped ribbon around a solid core, maximizes flow
capacity with minimum pressure drop. Standard construction includes cast
aluminum, cast steel, and 316 stainless steel body materials suitable for most
environments. The tube bank is available in aluminum, 304 stainless steel and
316 stainless steel as standard. Gasketed for maximum 50 psig static pressure.
For higher pressure consult factory.
Periodic inspection, maintenance and
replacement of tube bank is as simple as removing tie-bolts and expanding the
remaining jack screws. Once the body sections are expanded, the tube bank and
shell are easily removed.
Available with flat face flanges for aluminum or
raised face flanges for cast steel and stainless steel to match ANSI, DIN, or
JIS 10K specifications.
|